표준 상세 조회
Home > 표준소개 > 품목별 적용표준 조회 > 표준 상세 조회
표준번호 IEC 62271-102    
품목 개폐기
표준명(한글) 고압 개폐장치 및 제어장치-제102부:교류용 단로기 및 접지개폐기
표준명(영문)
제정일 2001-12-19 (Valid)
최종 개정 확인일 2018-02-16 (Valid)
적용범위 This part of IEC 62271 applies to alternating current disconnectors and earthing switches, designed for indoor and outdoor enclosed and open terminal installations for voltages above 1 000 V and for service frequencies up to and including 60 Hz.
인용표준(규격) - IEC 60137:1995, Insulating bushings for alternating voltages above 1 000 V
- IEC 60265-1:1998, High-voltage switches - Part 1: Switches for rated voltages above 1 kV and less than 52 kV
- IEC 60265-2:1988, High-voltage switches - Part 2: High-voltage switches for rated voltages of 52 kV and above
- IEC 60298:1990, A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
- IEC 60466:1987, A.C. insulation-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 38 kV
- IEC 60517:1990, Gas-insulated metal-enclosed switchgear for rated voltages of 72,5 kV and above
- IEC 60694:1996, Common specifications for high-voltage switchgear and controlgear standards
- IEC 60865-1:1993, Short-circuit currents - Calculation of effects - Part 1: Definitions and calculation methods
- IEC 62271-1:2007, High-voltage switchgear and controlgear - Part 1: Common specifications
- IEC 62271-100:2008, High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers
- ISO 2768-1:1989, General tolerances - Part 1: Tolerances for linear and angular dimensions without individual tolerance indications
정격구분 Clause 4 of IEC 60694 is applicable with the following additions to the list of ratings:
k) rated short-circuit making current (for earthing switches only);
l) rated contact zone (for divided support disconnectors only);
m) rated mechanical terminal load; and for rated voltages 52 kV and above:
n) rated values of the bus-transfer current switching capability of disconnectors;
o) rated values of the induced current switching capability of earthing switches.
주요 시험항목 Type tests
Clause 6 of IEC 60694 is applicable with the following additions:

Grouping of tests
Subclause 6.1.1 of IEC 60694 is applicable with the following additions to the mandatory type tests given in IEC 60694:
Mandatory type tests:
- tests to prove satisfactory operation and mechanical endurance (6.102) (M); Optional type tests:
- tests to prove the short-circuit making performance of earthing switches (6.101);
- tests to prove satisfactory operation under severe ice conditions (6.103);
- tests to prove satisfactory operation at temperature limits (6.104);
- tests to verify the proper function of position indicating devices (6.105 and annex A);
- tests to prove the bus-transfer current switching capability of disconnectors (6.106 and annex B);
- tests to prove the induced current-switching capability of earthing switches (6.107 and annex C);
- tests to prove the bus-charging current switching ability of disconnectors used in metal enclosed switchgear (6.108 and annex F).

Routine tests
Clause 7 of IEC 60694 is applicable with the following additions:
Addition to the list of routine tests:
f) Mechanical operating tests in accordance with 7.101.
If test reports of routine tests are required by agreement between manufacturer and user, from manufacturers whose system of quality assurance has been certified, reports according to their quality hand book are acceptable.
표준이력
No. Date Publication Edition Status
1 2001-12-19 IEC 62271-102:2001 1.0 Valid
2 2002-04-30 IEC 62271-102:2001/COR1:2002 1.0 Valid
3 2003-05-27 IEC 62271-102:2001/COR2:2003 1.0 Valid
4 2005-02-23 IEC 62271-102:2001/COR3:2005 1.0 Valid
5 2011-08-19 IEC 62271-102:2001/AMD1:2011 1.0 Valid
6 2012-01-27 IEC 62271-102:2001/AMD1:2011/COR1:2012 1.0 Valid
7 2012-02-15 IEC 62271-102:2001+AMD1:2011 CSV 1.1 Valid
8 2013-02-14 IEC 62271-102:2001/AMD2:2013 1.0 Valid
9 2013-02-14 IEC 62271-102:2001+AMD1:2011+AMD2:2013 CSV 1.2 Valid
10 2014-06-05 IEC 62271-102:2001/COR4:2014 1.0 Valid
11 2018-02-16 IEC 62271-102:2018 PRV 2.0 Valid
공인검수면제 대상업체 세광전기, 신우전기제조㈜